Chiller EIR default rated condition and curves don't match #2093

Open

Description

@jmarrec

The Default Chiller:ElectricEIR creates has a problem... At the rated conditions, the CAPFT and EIRFT will return a value different than 1.

model = OpenStudio::Model::Model.new
chiller = OpenStudio::Model::ChillerElectricEIR.new(model)
ref_lchwt = chiller.referenceLeavingChilledWaterTemperature
ref_ecnwt = chiller.referenceEnteringCondenserFluidTemperature
eirft = chiller.electricInputToCoolingOutputRatioFunctionOfTemperature

# EIRFT is wrong
eirft.evaluate(ref_lchwt, ref_ecnwt)
# => 0.8614399290202399

# CAPFT is wrong
capft = chiller.coolingCapacityFunctionOfTemperature
capft.evaluate(ref_lchwt, ref_ecnwt)
# => 1.0554712015060401

# EIRFPLR is ok
eirfplr = chiller.electricInputToCoolingOutputRatioFunctionOfPLR
eirfplr.evaluate(1)
# => 1.00138225

Activity

  1. added this to the Version 1.11.0 milestone on Feb 24, 2016
  2. kbenne commented on Mar 17, 2016

    @kbenne
    Contributor

    @jmarrec I received data from you on the water cooled chiller. Do you have similar for air cooled?

  3. jmarrec commented on Mar 19, 2016

    @jmarrec
    CollaboratorAuthor

    Kyle,

    I don't remember what I gave you exactly. I know it was at least the doe2 default chiller but also a couple more.

    What do you need? (Knowing that I'm still on vacation and without access to a computer)

    I have all the chillers from the EnergyPlus data set in osc format (need to find time to upload them to bcl with the bcl gem), but I think so do you: I suggest picking one there.
    For air cooled, as far as I remember there aren't a lot of them, I'd start looking at the example files to find data (search with a regex for all chillers having a condenser type to air cooled for example

    Envoyé de mon iPhone

    Le 18 mars 2016 à 02:41, Kyle Benne notifications@github.com a écrit :

    @jmarrec I received data from you on the water cooled chiller. Do you have similar for air cooled?

    —
    You are receiving this because you were mentioned.
    Reply to this email directly or view it on GitHub

  4. kbenne commented on May 26, 2016

    @kbenne
    Contributor

    @jmarrec I thought I took care of this, but there is no record on the issue here. Can you confirm that this is what you want?

  5. jmarrec commented on May 29, 2016

    @jmarrec
    CollaboratorAuthor

    Sounds good to me. Have you run a test model to see if the warning "curve out of bound" pops up or not?

  6. MatthewSteen commented on Aug 2, 2016

    @MatthewSteen
    Member

    Dropping in an air-cooled chiller to 1.12.0 results in a warning for the EIRFTemp.

    ** Warning ** GetElectricEIRChillerInput: Chiller:Electric:EIR="CHILLER - AIR COOLED"
       **   ~~~   ** Energy input ratio as a function of temperature curve output is not equal to 1.0 (+ or - 10%) at reference conditions.
       **   ~~~   ** Curve output at reference conditions = 0.850
    
  7. macumber commented on Nov 29, 2016

    @macumber
    Contributor

    @kbenne is this complete?

  8. jmarrec commented on Sep 28, 2017

    @jmarrec
    CollaboratorAuthor

    Still the case in 2.2.1 today, same warning as @MatthewSteen gave above.

  9. removed this from the Version 1.14.0 milestone on Jan 13, 2018
  10. jmarrec commented on Sep 21, 2018

    @jmarrec
    CollaboratorAuthor

    Ok, so first problem is that the Aircooled chiller doesn't have a hardcoded Reference condenser temperature, so it ses 85F which is the standard rating temp for a WATER COOLED Chiller (EWT°F), whereas air cooled is 95F (OAT DB °F).

    Second, the curve don't look one bit like what I would expect. Looking at EIRFPLR, from the E+ example "AirCooledChiller.idf' (I took the first one I found that didn't have a curve y=x), from the openstudio-standards file for 90.1-2013, and from comnet and from the current openstudio library "Air Cooled Chiller":

    image

    'Comnet-AirCooled-Scroll' and 'AirCooled Chiller WithoutCondenser 150-9999tons 1.2kW/ton' appear to be the same.

  11. jmarrec commented on May 14, 2020

    @jmarrec
    CollaboratorAuthor
  12. joseph-robertson commented on Jul 23, 2025

    @joseph-robertson
    Collaborator

    Chiller:Electric:ReformulatedEIR follows the example IDF curve values from https://bigladdersoftware.com/epx/docs/25-1/input-output-reference/group-plant-equipment.html#chillerelectricreformulatedeir.

    Chiller:Electric:EIR does not follow the example IDF curve values from https://bigladdersoftware.com/epx/docs/25-1/input-output-reference/group-plant-equipment.html#chillerelectriceir. Should it?

  13. joseph-robertson commented on Jul 23, 2025

    @joseph-robertson
    Collaborator

    Both eirft.evaluate(ref_lchwt, ref_ecnwt) and capft.evaluate(ref_lchwt, ref_ecnwt) evaluate to 1.0 if ref_ecnwt=35 (95F).